FED-STD-791D
6.6 Carefully add a fresh 95-mL sample of the fuel to be tested and seal the sample bottle
with the plastic screw cap as before.
6.7 Repeat the shaking, settling, rating, and siphoning steps as described in 6.3 through
6.6 until ten cycles (or extractions) have been performed.
7. CALCULATIONS
7.1 This section is not applicable to the test procedure.
8. REPORTING
8.1 Report interface ratings as measured above. A rating of 3 or greater, denoting the
presence of water-reactive impurities is considered unsatisfactory. The initial formation of these
stable interfacial emulsions are indicative of potential filter-plugging and storage problems.
9. PRECISION
9.1 Precision data have not been developed for this method.
Method Prepared By:
Army - ME - 1986
64