MIL-ST0-1518E
TABLE I. Sampling requirements and test limits - Continued.
ITEM |
SAMPLE POINT |
TEST |
TEST LIMITS |
SAMPLE FREQUENCY |
2. |
Tank Truck/Car Receipts. |
|||
2a. |
Receiving header upstream of any filtration. |
Solids/0P. Color and particle assessment method (ASTM 02276 Appendix 3) |
See Note 1. |
One sample daily from one T/T or T/C from each supplier. |
FSII. (ASTM 05006) (when additized) |
See TABLE II. |
|||
Conductivity. (when additized) |
See TABLE II. |
|||
Flash Point. |
See TABLE II. |
|||
2b. |
0ownstream of filter separator if installed. |
Solids/0P. Color and particle assessment method (ASTM 02276 Appendix 3) |
See Note 1. |
Every 7 days or next receipt. Take one downstream sample in conjunction with any one of the upstream samples, compare the results. |
3. |
Storage tanks. |
Conductivity. (ASTM 02624) (when additized) |
50 - 700 CU. |
Every 14 days. |
FSII. (ASTM 05006) (when additized) |
See TABLE II. |
|||
4. |
Refueling truck fillstand. 0ownstream of filter separator. |
Solids/0P. Color and particle assessment method (ASTM 02276 Appendix 3) |
See Note 1. |
Every 7 days. If fillstand is inactive for more than one week, sample during the first refueler fill. Sample during first refueler fill after F/S elements are changed. |
Water. (ASTM 03240) |
10 ppm. |
16